Shifting Input Values

 Shifting Inputs
You can set the Process Value Slope Coefficient and Process Value Input Shift parameters to
compensate the PV.
Process Value Input Shift
Process Value Slope Coefficient
• Calculating the Process Value Slope Coefficient and Process Value Input Shift
In the following equation, PVi is the input to the calculation, PVo is the result, INRT is the process
value slope coefficient, and INS is the process value input shift: PVo = (PVi × INRT) + INS
 Moving Average
• The moving average operation reduces sudden changes in the input due to noise and other
factors, and can be enabled separately for each input.
• The Moving Average Count parameter is used for the moving average. It can be set to OFF, 2, 4,
8, 16, or 32.
• The default is OFF (disabled).*
Input data
Parameter
Moving Average Count
* The default is 8 for models other than the E5D--8.
 Input Digital Filter
You can use the input digital filter to help remove the noise component from input signals.
If you set the Input Digital Filter parameter to any value other than 0.0, the filter works as a robust
filter to reduce high-frequency noise.
PV before passing through filter
A
(Time constant)
E5@D Digital Temperature Controllers User's Manual (H224)
Parameter
Temperature input: −199.9 to 999.9
Analog input: −1,999 to 9,999
0.001 to 9.999
MASK8
Time
Setting range
OFF, 2, 4, 8, 16, or 32
PV after passing
through filter
0.63A
Time
Input digital filter
Setting range
0.0 to 999.9
Setting range
Operation result
Unit
Times
Unit
Seconds
5 Advanced Operations
Unit
Default
°C or °F
0.0
EU
None
1.000
Default
OFF*
Default
0.0
0
5
5 - 25