Omron E5*D series User Manual page 369

Digital temperature controllers
Hide thumbs Also See for E5*D series:
Table of Contents

Advertisement

[[[[
]]]]
 Meaning
Though this is not an error, it is displayed if the process value exceeds the display range when the
control range is larger than the display range.
The display ranges are shown below (with decimal points omitted).
• When less than −1,999: [[[[
• When more than 9,999: ]]]]
 Operation
Control continues, allowing normal operation. The value will appear in the display for the PV.
Resistance thermometer input (Except for models with a
setting range of −199.9 to 500.0°C)
Thermocouple input (Except for models with a setting range of
−199.9 to 400.0°C)
ES1B
Control range
s.err display
Numeric display
Input indication range
Analog Input
• When display range < control range
s.err display
[[[[ display
e333
 Meaning
There is an error in internal circuits.
 Action
First, turn the power OFF then back ON again. If the display remains the same, the Digital Controller
must be repaired. If the display is restored, then the probable cause is electrical noise affecting the
control system. Check for electrical noise.
 Operation
The control, auxiliary, and transfer outputs turn OFF. (A linear current output will be approx. 0 mA.)
E5@D Digital Temperature Controllers User's Manual (H224)
Display Range Exceeded
s.err display
Control range
Numeric display
]]]] display
Input indication range
−1999
9999
Display range*
AD Converter Error
Resistance thermometer input (Except for models with a
setting range of −1999. to 500.0°C)
Thermocouple input (Except for models with a setting range of
−199.9 to 400.0°C)
[[[[ display
s.err display
Analog Input
• When display range ≥ control range
s.err display
s.err display
*The display range is shown in numbers with decimal points omitted.
A Appendices
Control range
Numeric display
s.err display
Input indication range
Control range
Numeric display
s.err display
Input indication range
1999
9999
Display range*
A
A - 17

Advertisement

Table of Contents
loading

Table of Contents