Parameter
Proportional
Setting
Band
Integral Time * Integral/
Derivative
Time *
*
 Related Parameters
See
See
AT Execute/Cancel (Adjustment Level): Page 6-18
Integral/Derivative Time Unit (Advanced Function Setting Level): Page 6-68
c-p
c-i
c-d
These parameters set the PID constants for cooling control. These parameters are auto-
matically set according to the Heating/Cooling Tuning Method parameter when AT is exe-
cuted.
Function
Parameter
Proportional
Setting
Band (Cooling)
Integral Time
(Cooling) *
Derivative Time
(Cooling)*
*
 Related Parameters
See
See
AT Execute/Cancel (Adjustment Level): Page 6-18
Integral/Derivative Time Unit (Advanced Function Setting Level): Page 6-68
E5@D Digital Temperature Controllers User's Manual (H224)
Temperature input
Analog input
Standard or heating/cooling
Derivative
control
Time Unit of
1 s
Integral/
Standard or heating/cooling
Derivative
control
Time Unit of
0.1 s
Integral/Derivative Time Unit of 1 s
Integral/Derivative Time Unit of 0.1 s
The unit is determined by the setting of the Integral/Derivative Time Unit parameter. The
Proportional Band, Integral Time, and Derivative Time parameters are initialized if the
Integral/Derivative Time Unit parameter is changed.
Proportional Band (Cooling)
Integral Time (Cooling)
Derivative Time (Cooling)
Temperature input
Analog input
Integral/Derivative Time Unit of 1 s
Integral/Derivative Time Unit of 0.1 s 0.0 to 999.9
Integral/Derivative Time Unit of 1 s
Integral/Derivative Time Unit of 0.1 s 0.0 to 999.9
The unit is determined by the setting of the Integral/Derivative Time Unit parameter. The
Proportional Band (Cooling), Integral Time (Cooling), and Derivative Time (Cooling)
parameters are initialized if the Integral/Derivative Time Unit parameter is changed.
Setting range
0.1 to 999.9
0 to 9999
0.0 to 999.9
0 to 9999
0.0 to 999.9
The control must be set to heating/cooling control
and 2-PID control.
Setting range
0.1 to 999.9
0 to 9999
0 to 9999
6 Parameters
Unit
Default
°C
8.0
°F
14.4
%FS
10.0
Seconds
233
Seconds
233.0
Seconds
40
Seconds
40.0
Unit
Default
°C
8.0
°F
14.4
%FS
10.0
Seconds
233
Seconds
233.0
Seconds
40
Seconds
40.0
6 - 27