6 Parameters
sprt
sprl
• These parameters set the rate of change during SP ramp operation. They set the
maximum permissible change width per unit of time as the SP ramp set value and the SP
ramp fall value. The SP ramp function is disabled if this parameter is set to OFF.
Function
• For a temperature input, the decimal point positions of the SP ramp set value and SP
ramp fall value depend on the currently selected sensor, and for an analog input they
depend on the Decimal Point parameter.
SP Ramp Set Value
Setting
SP Ramp Fall Value
ol-h
ol-l
The MV Upper Limit and MV Lower Limit parameters set the upper and lower limits of the manipulated
variable. When the calculated manipulated variable exceeds the upper or lower limit value, the upper
or lower limit value will be the output level.
Function
• MV Upper Limit
Setting
Standard
Heating/cooling control
• MV Lower Limit
The MV for the cooling control output during heating/cooling control is expressed as a
negative value.
Standard
Heating/cooling control
 Related Parameters
See
See
PID ON/OFF (Initial Setting Level): Page 6-43
6 - 34
SP Ramp Set Value
MASK8
SP Ramp Fall Value
Parameter
OFF or 1 to 9,999
SAME (Same as SP ramp
set value), OFF or 1 to 9,999
MV Upper Limit
MV Lower Limit
Control method
Control method
Setting range
EU/s, EU/ min, EU/h
EU/s, EU/ min, EU/h
The control must be set to 2-PID control.
Setting range
MV lower limit + 0.1 to 105.0
0.0 to 105.0
Setting range
−5.0 to MV upper limit − 0.1
−105.0 to 0.0
E5@D Digital Temperature Controllers User's Manual (H224)
Unit
Default
OFF
SAME
Unit
Default
%
100.0
Unit
Default
%
0.0
−100.0