Omron E5*D series User Manual page 312

Digital temperature controllers
Hide thumbs Also See for E5*D series:
Table of Contents

Advertisement

6 Parameters
lba
This parameter enables or disables the LBA function and sets the detection time interval.
• To disable the LBA function, set 0.
Function
Setting
 Related Parameters
See
See
Alarm 1 to 4 Type (Initial Setting Level): Page 6-50
LBA Level (Advanced Function Setting Level): Page 6-78
LBA Band (Advanced Function Setting Level): Page 6-79
lbal
• This parameter sets the LBA level.
• If the deviation between the SP and PV exceeds the LBA level, a loop burnout is
detected.
Function
Temperature input
Setting
Analog input
 Related Parameters
See
See
Process Value/Set Point (Operation Level): Page 6-8
Alarm 1 to 4 Type (Initial Setting Level): Page 6-50
LBA Detection Time (Advanced Function Setting Level): Page 6-78
LBA Band (Advanced Function Setting Level): Page 6-79
6 - 78
LBA Detection Time
Setting range
0 to 9999
LBA Level
Setting range
0.1 to 999.9
0.01 to 99.99
Alarm 1 must be assigned.
The alarm type must be set to 12 (LBA).
Unit
Default
Seconds
0
Alarm 1 must be assigned.
The alarm type must be set to 12 (LBA).
The LBA detection time must not be 0.
Unit
°C
°F
%FS
E5@D Digital Temperature Controllers User's Manual (H224)
Default
8.0
14.4
10.00