prst
This parameter starts and stops the simple program function.
• The RUN/STOP status will automatically switch to RUN when this parameter is set to
STRT.
• The simple program will stop when this parameter is set to RSET.
Function
• This parameter will function as a monitor display for the start/stop status of the simple
program if an event input is selected to start the simple program.
RSET
Operation
STRT
 Related Parameters
See
See
Soak Time Remain (Operation Level): Page 6-12
RUN/STOP (Operation Level): Page 6-12
Soak Time (Adjustment Level): Page 6-32
Wait Band (Adjustment Level): Page 6-32
Program Pattern (Initial Setting Level): Page 6-48
Soak Time Unit (Advanced Function Setting Level): Page 6-83
E5@D Digital Temperature Controllers User's Manual (H224)
Program Start
Setting range
Stops the simpler program.
Starts the simpler program.
The Program Pattern parameter must not be set to
OFF.
Default
rset
6 Parameters
6
6 - 11