Omron E5*D series User Manual page 283

Digital temperature controllers
Hide thumbs Also See for E5*D series:
Table of Contents

Advertisement

cp
c-cp
• These parameters set the output periods. Set the control periods taking the control
characteristics and the electrical life of the relay into consideration.
• For standard control, use the Control Period (Heating) parameter. The Control Period
Function
(Cooling) parameter cannot be used.
• When the heating control output is a current output, the Control Period (Heating)
parameter cannot be used. Also, when the cooling control output is a current output, the
Control Period (Cooling) parameter cannot be used.
• For heating/cooling control, the control period can be set independently for heating and
cooling. The Control Period (Heating) parameter is used for the heating control output,
and the Control Period (Cooling) parameter is used for the cooling control output.
Parameter name
Control Period
Setting
(Heating)
Control Period
(Cooling)
 Related Parameters
See
See
PID ON/OFF (Initial Setting Level): Page 6-43
E5@D Digital Temperature Controllers User's Manual (H224)
Control Period (Heating)
Control Period (Cooling)
Setting range
0.1, 0.2, 0.5, 1 to 99
0.1, 0.2, 0.5, 1 to 99
The heating and cooling control outputs must be
assigned to relay or voltage outputs (for driving
SSR).
The control must be set to 2-PID control.
For the Control Period (Cooling) parameter, the
control must be set to heating/cooling control.
Unit
Seconds
20 for relay output
2 for voltage output (for driving
SSR)
Seconds
20 for relay output
2 for voltage output (for driving
SSR)
6 Parameters
Default
6 - 49
6