Panel Cutout (Unit: Mm) - Omron E5*D series User Manual

Digital temperature controllers
Hide thumbs Also See for E5*D series:
Table of Contents

Advertisement

2 Preparations
2-1-2

Panel Cutout (Unit: mm)

 E5CD/E5CD-B
Individual Mounting
+0.6
45
0
 E5ED/E5ED-B
Individual Mounting
+0.6
45
0
• Waterproofing is not possible when group mounting several Digital Controllers.
• The recommended panel thickness is 1 to 5 mm for the E5CD and E5CD-B and 1 to 8 mm for E5ED
and E5ED-B.
• Digital Controllers must not be group mounting vertically. (Observe the recommended mounting
space limits.)
• When two or more Digital Controllers are mounted, make sure that the ambient temperature of the
Digital Controllers does not exceed the allowable operating temperature specified in the
specifications.
2 - 4
Group Mounting
(48 × number of Units − 2.5)
Group Mounting
*1
(48 × number of Units − 2.5)
+1.0
0
+1.0
0