 Switching 100% AT Execute/Cancel
When the Event Input Assignment parameter is set to AT-2 (100% AT Execute/Cancel), 100% AT
will be executed when the event input turns ON and will be cancelled when the input turns OFF.
Setting
Event input
Event input
 Switching 40% AT Execute/Cancel
When the Event Input Assignment parameter is set to AT-1 (40% AT Execute/Cancel), 40% AT will
be executed when the event input turns ON and will be cancelled when the input turns OFF.
Setting
Event input
Event input
 Switching Setting Change Enable/Disable
When the Event Input Assignment parameter is set to WTPT (Setting Change Enable/Disable), the
setting change will be disabled when the event input turns ON and will be enabled when the input
turns OFF.
Setting
Event input
Event input
 Switching Communications Write Enable/Disable
When the Event Input Assignment parameter is set to CMWT (Setting Change Enable/Disable),
writing with communications will be enabled when the event input turns ON and writing with
communications will be disabled when the event input turns OFF.
Setting
Event input
Event input
 Switching Alarm Latch Cancel
When the Event Input Assignment parameter is set to LAT (Alarm Latch Cancel), all alarm latches
(alarms 1 to 4, heater burnout, HS alarm, latch) will be cancelled when event input turns ON.
Setting
Event input
Event input
 Performing PID Update (Adaptive Control)
When the Event Input Assignment parameter is set to A-UD (PID Update), updating PID constants
for adaptive control is started when the event input turns ON.
Setting
Event input
Event input
E5@D Digital Temperature Controllers User's Manual (H224)
Input contact
Status
OFF
100% AT cancelled
ON
100% AT executed
Input contact
Status
OFF
40% AT cancelled
ON
40% AT executed
Input contact
Status
OFF
Enabled
ON
Disabled
Input contact
Status
OFF
Disabled
ON
Enabled
Input contact
Status
OFF
---
ON
Cancelled
Input contact
Status
OFF
---
ON
Updated