Switching 100% AT Execute/Cancel
When the Event Input Assignment parameter is set to AT-2 (100% AT Execute/Cancel), 100% AT
will be executed when the event input turns ON and will be cancelled when the input turns OFF.
Setting
Event input
Event input
Switching 40% AT Execute/Cancel
When the Event Input Assignment parameter is set to AT-1 (40% AT Execute/Cancel), 40% AT will
be executed when the event input turns ON and will be cancelled when the input turns OFF.
Setting
Event input
Event input
Switching Setting Change Enable/Disable
When the Event Input Assignment parameter is set to WTPT (Setting Change Enable/Disable), the
setting change will be disabled when the event input turns ON and will be enabled when the input
turns OFF.
Setting
Event input
Event input
Switching Communications Write Enable/Disable
When the Event Input Assignment parameter is set to CMWT (Setting Change Enable/Disable),
writing with communications will be enabled when the event input turns ON and writing with
communications will be disabled when the event input turns OFF.
Setting
Event input
Event input
Switching Alarm Latch Cancel
When the Event Input Assignment parameter is set to LAT (Alarm Latch Cancel), all alarm latches
(alarms 1 to 4, heater burnout, HS alarm, latch) will be cancelled when event input turns ON.
Setting
Event input
Event input
Performing PID Update (Adaptive Control)
When the Event Input Assignment parameter is set to A-UD (PID Update), updating PID constants
for adaptive control is started when the event input turns ON.
Setting
Event input
Event input
E5@D Digital Temperature Controllers User's Manual (H224)
Input contact
Status
OFF
100% AT cancelled
ON
100% AT executed
Input contact
Status
OFF
40% AT cancelled
ON
40% AT executed
Input contact
Status
OFF
Enabled
ON
Disabled
Input contact
Status
OFF
Disabled
ON
Enabled
Input contact
Status
OFF
---
ON
Cancelled
Input contact
Status
OFF
---
ON
Updated