This parameter sets the initial value of the manual MV to use after control moves from Auto-
matic Mode to Manual Mode.
Function
Standard control: −5.0 to 105.0
Setting
Heating/cooling control: −105.0 to 105.0
If the Manual MV Limit Enable parameter is set to ON, the setting range will be the MV
lower limit to the MV upper limit.
Related Parameters
See
See
Manual Output Method (Advanced Function Setting Level): Page 6-74
Manual MV Limit Enable (Advanced Function Setting Level): Page 6-84
E5@D Digital Temperature Controllers User's Manual (H224)
Manual MV Initial Value
Setting range
The control must be set to 2-PID control.
Unit
Default
%
0.0
6 Parameters
6
6 - 75