Omron E5*D series User Manual page 311

Digital temperature controllers
Hide thumbs Also See for E5*D series:
Table of Contents

Advertisement

hsl
• When this parameter is set to ON, the HS alarm is held until any of the following
conditions is satisfied.
Function
• Output is turned OFF when switching to the Initial Setting Level, Communications Setting
Level, Advanced Function Setting Level, or Calibration Level.
Setting
 Related Parameters
See
See
HS Alarm Use (Advanced Function Setting Level): Page 6-76
Event Input Assignment 1 to 4 (Initial Setting Level): Page 6-57
HB ON/OFF (Advanced Function Setting Level): Page 6-66
PF Setting (Advanced Function Setting Level): Page 6-86
hsh
• This parameter sets the hysteresis for HS alarms.
Function
Setting
 Related Parameters
See
See
HS Alarm Use (Advanced Function Setting Level): Page 6-76
E5@D Digital Temperature Controllers User's Manual (H224)
HS Alarm Latch
a The HS alarm current is set to 50.0 A.
b The power is cycled.
c The latch is cancelled by the PF Key.
(PF Setting = LAT: Alarm Latch Cancel)
d The latch is cancelled by an event input.
(Event Input Assignment 1 to Event Input Assignment 4 = LAT: Alarm Latch
Cancel)
Setting range
on: Enabled, off: Disabled
HS Alarm Hysteresis
Setting range
0.1 to 50.0
HB and HS alarms must be supported.
The HS Alarm Use parameter must be set to ON.
Default
off
HB and HS alarms must be supported.
The HS Alarm Use parameter must be set to ON.
The HS Alarm Latch parameter must be set to OFF.
Unit
Default
A
0.1
6 Parameters
6
6 - 77