5-25 Setting the Operating Status to Use
When Power Is Turned ON
You can set the operating status to use when the power supply is turned ON (including software
resets).
You can set this with the p-on (Operation After Power ON) parameter in the Initial Setting Level. The
default setting is to continue (the same status as when power was interrupted).
You can set any of the following options.
Operating status
Continue (default)
Stop
Manual
 Parameters
Parameter
Operation After
Power ON
Note: Priority of Event Inputs
• If an event input is assigned to RUN/STOP, the setting of the Operation After Power ON
parameter (STOP) will be given priority.
• If an event input is assigned to Auto/Manual, the Auto/Manual specification of the event input will
be given priority over the setting of the Operation After Power ON parameter (Manual).
Operating Procedure
The following example shows how to set the Digital Controller to stop control when the power supply is turned ON.
• Setting the Operation After Power ON Parameter
1
Press the M Key several times in the Initial Setting Level to
display p-on (Operation After Power ON).
The default is cont (continue).
2
Press the U or D Key to set the parameter to stop (stop).
E5@D Digital Temperature Controllers User's Manual (H224)
The status when power was interrupted is continued.
• If operation (run) was in progress when power was interrupted, operation will
start.
• If control was stopped (stop) when power was interrupted, control will be stopped.
• If Manual Mode was in progress when power was interrupted, Manual Mode will
be entered.
Control will be stopped (stop).
Manual Mode will be entered.
Display
cont: Continue (status at power OFF)
p-on
stop: Control stopped (stop)
manu: Manual Mode
5 Advanced Operations
Description
Setting range
Default
Level
Initial
cont
Setting
Level
Initial Setting Level
p-on
Operation After
Power ON
cont
p-on
stop
5 - 85
5