Wiring The Additional Nx Unit Power Supply Unit; Wiring The Additional I/O Power Supply Unit; Wiring The Protective Devices; Grounding - Omron NX Series Hardware User Manual

Machine automation controller
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

Connect the DC power supply to the Unit power supply terminals.
Terminal number indi-
cation
A1, B1
A3, B3
The 24-V terminals and 0-V terminals are internally connected to each other.
You can use the unwired terminals for through-wiring to an Additional NX Unit Power Supply Unit or to
the Unit power supply terminals on another NX102 CPU Unit.
When you supply the Unit power through the unwired terminals, be careful not to exceed 4 A, the cur-
rent capacity of power supply terminals.
5-4-2

Wiring the Additional NX Unit Power Supply Unit

For information on wiring the Additional NX Unit Power Supply Unit, refer to the NX-series System
Units User's Manual (Cat. No. W523-E1-05 or later).
5-4-3

Wiring the Additional I/O Power Supply Unit

For information on wiring the Additional I/O Power Supply Unit, refer to the NX-series System Units
User's Manual (Cat. No. W523-E1-05 or later).
5-4-4

Wiring the Protective Devices

For information on wiring the protective devices to protect against short circuits and overcurrents of
external circuits, refer to 4-4-3 Selecting Protective Devices on page 4-24.
5-4-5

Grounding

This section describes how to ground the CPU Rack.
NX-series NX102 CPU Unit Hardware User's Manual (W593)
Terminal name
24 V
Connect the + terminal (24 VDC) of the Unit power supply to A1 or
B1.
0 V
Connect the - terminal (0 VDC) of the Unit power supply to A3 or
B3.
5 Installation and Wiring
Description
5