Changing From Local Control To External Control - Panasonic VF0 Series Instruction Manual

Compact inverter 400v class
Hide thumbs Also See for VF0 Series:
Table of Contents

Advertisement

To enable external control by an external switch or PLC, follow the
procedure below.
[Changing procedure]
STOP
MODE
•・•
SET
•・•
SET
SET
•・•
SET
MODE
Operation can be started when the data has been set.
<<Potentiometer: P09=2>>
65
Downloaded from
www.Manualslib.com
Changing from Local Control to
External Control
(1) Enabling external control for start/stop and forward/reverse
(To change parameter P08 from "0" to "2")
Press the STOP button to stop the inverter.
Press the MODE button three times.
Change from P01 to P08 using the ••
buttons.
Press the SET button.
Change from "0" to "2" using the ••
buttons.
Press the SET button and set the data.
This completes setting the data.
(2) Enabling external control for frequency setting signals
(0 to 10V)
(To change parameter P09 from "0" to "4".)
Press the SET button.
Change from "0" to "4" using the ••
buttons.
Press the SET button and set the data.
Press the MODE button.
<<0 to 5V: P09=3>>
1
2
10kΩ,
2
1/4W
(Min)
3
3
manuals search engine
.......................(Parameter P08)
Main display
0
0
P
0
P
0
P
0
....................(Parameter P09)
P
1
0
0
<<4 to 20mA: P09=5>>
+
+
2
0 to 5V
4 to 20mA
200Ω
-
-
3
[Terminal connection (P08=2)]
3
Common termional
0
ON : Start
5
OFF : Stop
1
ON : Reverse
6
OFF : Forward
8
<<When P08 = 3, 5>>
0
3
Common termional
2
ON
5
OFF : Stop
9
ON
6
OFF : Stop
0
[Terminal connection (P09=4)]
+
4
2
0 to 10V
0
-
3
0
(Important)
When using the 4 to 20mA
signal, always connect a "200Ω
resistor". The inverter could be
damaged if the 200Ω resistor is
not connected.
: Forward run
: Reverse run