P101£ºOV stop function select
When frequency setting signal is lower than data setting value, the inverter's output can be stopped
if the OV stop function is used effectively.
Data setting range (Hz)
•E Setting data value "0000": OV stop function is not provided.
•E Setting data "0.5~400.0": OV stop function is provided. (OV stop frequency setting)
[OV stop function]
•E If frequency setting signal is " analog setting (parameter P004 = "0","2","3","4","5","6") ", and
frequency setting value is below setting value of the OV stop function select, the inverter's
output will be stopped.
•E If the OV stop function select is set to "0000", the inverter wil not carry out OV stop.
When frequency setting signal is less than 1/100 (1%) full scale, the inverter will continuously
run at the lower frequency limit.
Frequency setting signal
Max£¬ 5 V£¬ 1 0V£¬ 2 0mA£¬
Min£¬ 0V£¬ 0V£¬4mA£¬
Run signal
Max. output frequency
Output
frequency
* A and B are in
OV stop state.
Note
•EWhen frequency setting signal is set with digits or communication, the inverter will not carry
out OV stop.
•EWhen frequency setting signal is less than 1/100 (1%) full scale, command value will change
to 0Hz.
0000•E0.5 to 400.0
[When P101 = 0.5~400]
20mA
Setting
value
0mA
0
AB
[When P101 = 0000]
100%
Related
parameters
100%
Lower
frequency clamp
P004, P099
P125
111