Commissioning and use during operation
"Set points" menu
items
Set point
Only with analog or digital channels
Time span dt
Only for the "Gradient dy/dt" type
Time delay in
Time delay
Reason for change
In case of an active user management (FDA 21 CFR Part 11) the reason for changing the limit value has to be stated. The reason will
be saved in the event log/audit trail. In case of an inactive user management the stating of the reason is optional. Furthermore, the
old and the new value will be stored.
Please enter the reason for the change of the limit. This message will be stored inside the event log.
Accept set points
Accept all the modified set points here. Picklist: No, yes
96
Configurable parameters
(factory settings are highlighted in bold)
Only with analog channels: Enter the analog set point in the preset engineering unit, e.g.
in °C, bar, etc.
Only with digital channels: Enter the counter alarm set point in the engineering unit set
up, e.g. m, piece, etc.
Time span within which the signal has to change by the specified value so it can be
detected as a set point. Note: max. 60 seconds.
Set up which engineering units are to be used for the time delay.
In order to be interpreted as an alarm the signal must exceed or undercut the preset
value by at least the time set up.