Technical data
136
USB bar code reader reference list:
Datalogic Gryphon D230; Metrologic MS5100 Eclipse Series; Symbol LS2208
10.4.2
Ethernet interface (interface slot):
An IEEE 802.3-compatible connection is available on a shielded RJ45 plug connector on the rear of
the unit as the network connection. This can be used to connect the unit with a hub or switch to
units in an office environment. For safe spacing distances, the office equipment standard EN 60950
must be observed. The assignment corresponds to a standards-compliant MDI port (AT&T258) such
that a shielded 1:1 cable with a maximum length of 100 meters (328 ft) can be used here. The
Ethernet port is designed as 10/100–BASE–T. Direct connection to a PC is possible with a crossover
cable. Half-duplex and full-duplex data transfer is supported. Alternatively, a GPRS modem can also
be connected to the Ethernet interface.
The unit can be used in the network as a "Web server". Two Ethernet function LEDs on the rear of
the unit.
10.4.3
Serial RS232/RS485 interface (interface slot):
A combined RS232/RS485 connection is available on a shielded SUB D9 socket at the rear of the
unit. This can be used for data or program transfer and to connect a modem. For communication
via modem, we recommend an industrial modem with a watchdog function.
The following baudrates are supported: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Max. line length with shielded cable: 2 m (6.6 ft) (RS232) or 1000 m (3281 ft) (RS485)
Both interfaces are galvanically isolated from the system.
The RS232/RS485 interfaces cannot be used simultaneously.
• Modbus RTU master (optional):
As Modbus master, the device can scan other Modbus slaves via RS485.
10.4.4
Remote interrogation with analog or GSM/GPRS wireless
modem:
• Analog modem:
An analog modem (e.g. Devolo or WESTERMO), which is connected to the RS232 interface with
a special modem cable (see Accessories RXU10-A1), is recommended for industry.
• GSM/GPRS wireless modem:
A GSM/GPRS wireless modem (e.g. Siemens, INSYS or WESTERMO, incl. antenna and power
unit), which is connected to the RS232 interface with a special modem cable (RXU10-A1
accessory), is recommended for industry. Important: the wireless modem needs a SIM card and
data transfer subscription. In addition, it must be possible to deactivate the PIN prompt.
10.4.5
Bus interface (interface slot, optional)
• PROFIBUS–DP slave:
The unit can be integrated into a fieldbus system as per the PROFIBUS–DP standard by means of
the PROFIBUS-DP interface. Up to 40 analog inputs and 14 digital inputs can be transmitted via
PROFIBUS–DP and stored in the unit. For bidirectional communication in cyclic data transfer.
Baudrate: maximum 12 Mbit/s
• Modbus RTU slave:
Up to 40 analog inputs and 14 digital inputs can be transmitted via Modbus and stored in the unit.
• Ethernet Modbus TCP slave:
Connection to SCADA systems (Modbus master). Up to 40 analog inputs and 14 digital inputs
can be transmitted via Modbus and stored in the unit.
Advanced Graphic Data Manager