It is not permitted to mix low voltage and safety extra low voltage (do not mix SELV circuits
and low voltage).
Response time:
max. 400 ms
Maximum DC contact load:
30 V / 3 A
Maximum AC contact load:
230 V / 3 A
10.2.3
Analog and pulse outputs
Number:
Optional digital card (slot 5): 2 analog outputs which can be operated as current or pulse outputs.
Analog output (current output):
Output current: 0/4 to 20 mA with 10% overrange
Max. output voltage: approx. 16 V
Accuracy: 0.1% of output range
Temperature drift: 0.015%/K
Resolution: 13 bit
Load: 0 to 500 Ohm
Error signal to NAMUR NE43: 3.6 mA or 21 mA can be configured
Digital output (pulse output):
Output voltage as per IEC 61131-2:
5 V corresponds to LOW
12 V corresponds to HIGH
Short-circuit proof (maximum 25 mA)
Frequency: 0 to 2 kHz
Pulse width: 0.5 to 1000 ms
Accuracy: 0.1% of output range
Temperature drift: 0.1%
Load: 1 kOhm
10.2.4
Galvanic isolation
All the inputs and outputs are galvanically isolated from one another and tested with the following
testing voltages:
Relay
Relay
2.3 kV
Digital in
2.3 kV
Analog in
2.3 kV
Analog out
2.3 kV
Digital in
Analog in
2.3 kV
2.3 kV
1)
500 V
500 V
500 V
500 V
500 V
500 V
Technical data
Analog out
2.3 kV
500 V
500 V
500 V