Camille Bauer LINAX A325 Operating Instructions Manual page 71

Table of Contents

Advertisement

Advanced Graphic Data Manager
"Outputs" menu
items
Submenu: Measured value
correction
Only for signal "0/4-20 mA"
Submenu: Fault mode
Only for signal "0/4-20 mA"
Configurable parameters
(factory settings are highlighted in bold)
Here, you can correct the current value output (only required if the unit
processing the values further cannot balance possible measurement
section tolerances). Follow these instructions:
1. At the connected unit, read the value displayed in the lower and upper
measuring range.
2. Enter the lower and upper target and actual value.
Lower correction value
Target value: enter the target value here.
Actual value: here, enter the lower actual value that is displayed at the
connected unit.
Upper correction value:
Target value: enter the target value here.
Actual value: here, enter the upper actual value that is displayed at the
connected unit.
Specify how the analog output should behave in the event of a fault (e.g.
if the input channel has a cable open circuit).
Namur NE43
Switch outputting the 4 to 20 mA range as per NAMUR
Recommendation NE 43 on and off. The following error ranges apply
when NAMUR NE43 is switched on:
3.8 mA: under range
20.5 mA: overrange
3.6 mA or 21.0 mA: cable open circuit
Picklist: off, on
In the event of an error
What value should the output assume in the event of an error (e.g. cable
open circuit or calculated value invalid)?
Picklist: last valid value, range start, meas. range end, 3.6 mA, 21 mA,
free configuration
Error value
This value is output in the event of an error.
Note: the value must be between 0 and 22 mA. See table  Page 58
Commissioning and use during operation
51200/000 to
51200/001
51205/000 to
51205/001
51300/000 to
51300/001
51305/000 to
51305/001
51400/000 to
51400/001
51405/000 to
51405/001
51410/000 to
51410/001
Direct
access
code
71