Camille Bauer LINAX A325 Operating Instructions Manual page 56

Table of Contents

Advertisement

Commissioning and use during operation
"Inputs" menu
items
Submenu: Totalization
Only if "Free configuration" is
selected for "Calc. factor":
56
Configurable parameters
(factory settings are highlighted in bold)
Settings only required if this analog measuring point is to be integrated
for calculating the volume for example. For analysis periods, see "Signal
analysis".
Fig. 38:
Setup - Inputs - Universal inputs, Universal input x,
submenu "Totalization"
Totalization: using the totalization function, the volume (in m
calculated from an analog signal (e.g. flow in m
Picklist: no, yes
Totalization base: select the corresponding time base here. Example:
ml/s -> time base seconds (s); m
Picklist: second (s), minutes (min), hour (h), day (d)
Total. eng. unit: here, enter the unit for the volume determined by
3
totalization (e.g. "m
").
Low flow cut off: specify how the device should execute low flow cut
off.
Picklist: area around zero point, absolute value
Low flow cut off: analog values that are lower than the set threshold
value (absolute value) are not integrated ("low flow cut off").
User input: 6-digit; factory setting: 0
Calc. factor: factor for converting the integrated value (e.g. the
transmitter returns l/s -> integration base = second -> desired unit is m
-> select 0.001 as the factor).
Picklist: 0.00001 to 10000, free configuration; factory setting: 1
Calc. factor: user-defined entry of the factor for converting the
integrated value. Factory setting: 1.000
Totalizer: Initial setting for the totalizer. Useful when continuing
measurements recorded to date with an (electro)-mechanical counter.
Factory setting: 0
Advanced Graphic Data Manager
3
) can be
3
/h).
3
/h -> time base hours (h).
Direct access
code
24000/000 to
24000/039
24005/000 to
24005/039
24010/000 to
24010/039
24015/000 to
24015/039
24020/000 to
24020/039
24025/000 to
24025/039
24030/000 to
24030/039
24035/000 to
24035/039

Advertisement

Table of Contents
loading

Table of Contents