Output - Camille Bauer LINAX A325 Operating Instructions Manual

Table of Contents

Advertisement

Technical data
Converter resolution
Totalization
Number
Input level
Input frequency
Pulse length
Input current
Input voltage
Selectable functions
132
24 bit
The interim value, daily value, weekly value, monthly value, annual value and overall value can be
determined (13-digit, 64 bit).
10.1.2
Digital inputs
Standard version: 6 digital inputs
Optional digital card (slot 5): 8 additional digital inputs
To IEC 61131-2:
Logical "0" (corresponds to -3 to +5 V), activation with logical "1" (corresponds to +12 to +30 V)
Max. 25 Hz
Min. 20 ms
Max. 2 mA
Max. 32 V (steady-state, without destroying input)
Control input, ON/OFF message, pulse counter (13-digit, 64 bit), operating time,
message+operating time, quantity from time.
Functions of the control input: start recording, screensaver on, block setup, block keyboard/
navigator, time synchronization, change group, limit value monitoring on/off, individual LV on/off,
start/stop evaluation.
10.2

Output

10.2.1
Auxiliary voltage output
The auxiliary voltage is provided to activate the digital input (or the sensors) with floating contacts
and is galvanically isolated from the system and the inputs (testing voltage 500 V).
Output voltage:
24 V DC (±15%)
Output current:
Maximum 250 mA, short-circuit proof, not stabilized
10.2.2
Relay outputs
Standard version (power supply slot): 1 alarm relay with changeover contact, 5 relays with NO
contact e.g. for limit value alarms (can be configured as NC contact).
Optional digital card (slot 5): 6 additional relays with NO contact e.g. for limit value alarms (can be
configured as an NC contact).