Camille Bauer LINAX A325 Operating Instructions Manual page 55

Table of Contents

Advertisement

Advanced Graphic Data Manager
"Inputs" menu
items
Submenu: Measured value
correction
Configurable parameters
(factory settings are highlighted in bold)
For determining the correction values to offset measurement section
tolerances.
Follow these instructions:
1. Measure the current value at the lower measurement range.
2. Measure the current value at the upper measurement range.
3. Enter the lower and upper target and actual value.
Fig. 37:
Setup - Inputs - Universal inputs, Universal input x,
"Measured value correction" submenu
Lower correction value:
Target value: enter the lower target value here (e.g. measuring range
0°C to 100°C: 0°C).
Actual value: enter the lower value that is actually measured here (e.g.
measuring range 0°C to 100°C: 0.5°C measured).
Upper correction value:
Target value: enter the upper target value here (e.g. measuring range
0°C to 100°C: 100°C).
Actual value: enter the upper value that is actually measured here (e.g.
measuring range 0°C to 100°C: 100.5°C measured).
Correction RPT:
Rear panel temperature correction value for this universal input (only
required for thermocouples).
Note: Only appears once the service code has been entered!
Commissioning and use during operation
Direct access
23000/000 to
23000/039
23005/000 to
23005/039
23010/000 to
23010/039
23015/000 to
23015/039
23500/000
to
23500/039
code
55