Separate Networks - Christie J Series User Manual

J series
Hide thumbs Also See for J Series:
Table of Contents

Advertisement

Communication parameters, such as baud rate, must be set to match the particular controller device, before
connecting as a network. See the documentation that came with your controller device to determine the proper
baud rate. See
Section 3 Operation
set the Network Routing to RS-232 and RS-422 Joined.
NOTE: Connect only high quality, properly wired serial communication cables. Each RS-232 communication
cable should be no more than 50 feet in length.
Ethernet Network Setup: To add projectors to an Ethernet network, use standard CAT5 cables to connect
each projector Ethernet port to a hub on the network. A controller or PC must also be connected to the hub.
NOTE: A wireless router can be used to communicate to the projectors via 802.11b/g.
Setting the Projector IP Address, Subnet Mask and Gateway: See
Changing the Port Number: On some Ethernet networks, firewall restrictions may require that the port
number of the projector be changed from the default of 3002. If so, enter a new port number in the Ethernet
Settings menu or include the new port number.

2.5.7 Separate Networks

By default, communications which originate from one type of serial controller—RS-232 vs. RS-422 vs.
Ethernet—stay on the corresponding network path. A "separate" setting indicates this separation for Network
Routing in the Communications menu, see
controller, for example, it will communicate only with the projector to which it is connected unless you change
this setting to either RS-232 and RS-422 Joined or All Joined.
J Series 2.0, 2.4 and 3.0 kW User Manual
020-100707-03 Rev. 1 (02-2014)
for help changing the projector baud rate. To communicate to all projectors,
Section 4 Web User
Section 2: Installation and Setup
3.7 Optical Aperture.
Interface. If you are using an RS-422
2-27

Advertisement

Table of Contents
loading

This manual is also suitable for:

J 2.0 kwJ 2.4 kwJ 3.0 kw

Table of Contents