11.7 Output Terminal Function
It can be assigned the function No. in the following table to parameter f130 to f138, f157, f158.
Table of output terminal functions 1
Function
Code
No.
0
LL
Frequency lower limit
1
LLN
Inversion of frequency lower limit
2
UL
Frequency upper limit
3
ULN
Inversion of frequency upper limit
4
LOW
Low-speed detection signal
5
LOWN
Inversion of low-speed detection signal
6
RCH
Output frequency attainment signal
(acceleration/deceleration completed)
7
RCHN
Inversion of output frequency attainment
signal
(inversion of acceleration/deceleration
completed)
8
RCHF
Set frequency attainment signal
9
RCHFN
Inversion of set frequency attainment signal
10
FL
Fault signal (trip output)
11
FLN
Inversion of fault signal (inversion of trip
output)
14
POC
Over-current detection pre-alarm
15
POCN
Inversion of over-current detection pre-alarm
16
POL
Overload detection pre-alarm
17
POLN
Inversion of overload detection pre-alarm
20
POH
Overheat detection pre-alarm
21
POHN
Inversion of overheat detection pre-alarm
22
POP
Overvoltage detection pre-alarm
23
POPN
Inversion of overvoltage detection pre-alarm
24
MOFF
Power circuit undervoltage detection
25
MOFFN
Inversion of power circuit undervoltage
detection
26
UC
Small current detection
27
UCN
Inversion of small current detection
28
OT
Over-torque detection
29
OTN
Inversion of over-torque detection
Function
ON: Output frequency is more than
OFF: Output frequency is or less
Inversion of LL
ON: Output frequency is or more
OFF: Output frequency is less than
Inversion of UL
ON: Output frequency is or more
OFF: Output frequency is less than
Inversion of LOW
ON: Output frequency is within command frequency
OFF: Output frequency is more than command frequency
Inversion of RCH
ON: Output frequency is within ±
OFF: Output frequency is more than ±
Inversion of RCHF
ON: Inverter tripped
OFF: Inverter not tripped
Inversion of FL
ON: Output current is or more
OFF: Output current is less than
Inversion of POC
ON: (%) or more of calculated value of overload
protection level
OFF: Less than (%) of calculated value of overload
Inversion of POL
ON: Approx. 95C or more of IGBT element
OFF: Less than approx. 95C of IGBT element (90C or less
Inversion of POH
ON: Overvoltage limit in operation
OFF: Overvoltage detection canceled
Inversion of POP
ON: Power circuit undervoltage (MOFF) detected
OFF: Undervoltage detection canceled
Inversion of MOFF
ON: After output current comes to or less, value of
less than + for set time
OFF: Output current is more than
Inversion of UC
ON: After torque comes to or more, value of more
than - for set time
OFF: Torque is less than
Inversion of OT
K-35
Action
protection level
after detection is turned on)
(+ or more after detection turns on)
(-or less after detection turns on)
E6581697
Reference
5.10
6.1.1
7.2.2
6.1.2
7.2.2
6.1.3
7.2.2
6.24.2
3.5
7.2.2
11
6.15.5
6.24.13
6.24.7
6.24.9