Unverified Alarm Report
Enables / disables option unverified alarm report. When a cross zone is triggered, but no alarm
is created, system creates an unverified alarm in order to report. System reports unverified
alarms if option unverified alarm report is enabled.
7.3.5

Zone Indication Keypad and Event Log

Zones may be indicated on keypads and in event logs with a number that are different from
the zone number used for programming and hardware input.
One area system
Zones are indicated on keypads according to the zone numbers. When one zone is disable the
indication number of all following (higher) zone numbers will shift to a value decreased by
one.
Multi area system
Only zones assigned to one area are indicated on an area keypad in order beginning with 1
and by following the order of zone numbers.
Examples:
Examples:
AMAX 3000 / 4000: In a 1 Area or Area 1 system keypad zone number 17 should be indicated
on a 16 zone LED keypad. After disabling zone 16 (or another one in range 1 to 16) zone
number 17 is indicated on keypad as number 16.
AMAX 2100: In a one area system keypad zone number 17 should be indicated on an 8 zone
LED keypad. After disabling zone 5 zone number 17 is indicated on keypad as number 5.
Bosch Sicherheitssysteme GmbH
Installation Guide
Settings | en
59
2014.4 | 01 | F.01U.267.112