Bosch ICP-AMAX4-P1 Installation Manual page 51

Amax panel 4000; amax panel 4000 en
Hide thumbs Also See for ICP-AMAX4-P1:
Table of Contents

Advertisement

AMAX panel 4000 / AMAX panel 4000
EN
When the key-switch operates the arm / disarm, the keypad sounds two beeps and report sent
to the system by User Code 254
Notice!
As the key-switch operates the arm / disarm successfully, the siren sounds short to indicate
it.
11 – 24 Hour Fire
The Fire zone will perform as below:
1.
2.
3.
13 - Tamper
The tamper zone will perform as below:
1.
2.
3.
12- 24 Hour Fire with Verification (only possible for AMAX 4000 Zone 1)
The 24 - hour fire with verification zone will perform as below:
1.
2.
3.
14 - Bolt Contact
The Bolt-Contact zone will perform as below:
1.
Bosch Sicherheitssysteme GmbH
Disarm:
Zone normal - no alarm / no report
Zone triggered - alarm / report
AWAY Arm:
Zone normal - no alarm / no report
Zone triggered - alarm / report
Zone triggered - during exit time - alarm / report
Zone triggered - during entry time - alarm / report
STAY Arm: same as AWAY arm performance
A fire zone does not send a restore report until the zone is restored
Disarm:
Zone normal - no alarm / no report
Zone triggered - alarm / report
AWAY Arm:
Zone normal - no alarm / no report
Zone triggered - alarm / report
Zone triggered - during exit time - alarm / report
Zone triggered - during entry time - alarm / report
STAY Arm: same as AWAY arm performance
A tamper zone does not send a restore report until the zone is restored
Disarm:
Zone normal - no alarm / no report
Zone triggered: After the first alarm, the AMAX panel performs a fire verification reset
(10 seconds) and then waits a period up to two minutes for a second alarm. If a
second alarm occurs within this period, the AMAX panel indicates a fire alarm.
Otherwise, the AMAX panel resets back to its normal condition. At the end of the two
minute period an unverified fire alarm is logged and reported. A fire zone does not
send a restore report until the zone is restored
AWAY Arm: same as disarm performance
STAY Arm: same as disarm performance
Disarm:
Installation Guide
Settings | en
51
2014.4 | 01 | F.01U.267.112

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Icp-amax4-p2-enIcp-amax-p3-enAmax 4000Amax 4000en

Table of Contents