General

AMAX panel supports up to two communication modules.
The B426 Ethernet communication module supports monitored two-way IP communication via
Ethernet to perform alarm transmission, remote programming, and control of the AMAX panel.
Before installing B426, all power supplies (AC power supply and backup battery power
supply) of the AMAX panel should be disconnected. Use the standard three-hole installation
mode to install B426 in the enclosure of the AMAX panel or in another enclosure. To
reconfigure the module or connected to the alarm control panel with RPS, the network or
direct connection must be used to access its built-in Web server.
For more information about installation and configuration, see B426 Installation and Operating
Guide.
5.5.2

Address Setting

Turn the rotary switch to 6, i.e., set the address to 134 when the first B426 is used. Turn the
rotary switch to 9, i.e., set the address to 250 when the second B426 is used.
5.5.3

Wiring

Connect B426 to Bosch option Bus 1 or 2. The cable may not exceed 150 meters.
AMAX 2100 / 3000
AMAX 4000
Figure 5.7: Connecting B426 to the AMAX Panel
5.5.4

Status Indicator

B426 provides the following on-board LED indicators to help in troubleshooting.
On
Bosch Sicherheitssysteme GmbH
ITS-DX4020-G and B426 or B426 and B426
Blue system status indicator.
Green data bus indicator.
Green Ethernet link indicator.
LED Condition
Optional Modules and Peripheral Devices | en
B426
Trouble Condition
Installation Guide
Denotation
2014.4 | 01 | F.01U.267.112