2.20 Other function

2.20.1 Load torque high speed frequency control [Pr. 4, 5, 270 to 274]
Load torque high speed frequency control is a function
which automatically sets the operational maximum
frequency according to the load.
More specifically, the magnitude of the load is judged
according to the average current at a certain time after
[Pr.]
Name
4
Multi-speed setting (high speed)
5
Multi-speed setting (middle speed)
Stop-on contact/load torque high-
270
speed frequency control selection
High-speed setting maximum
271
current
272 Middle-speed setting minimum
current
273 Current averaging range
Current averaging filter time
274
constant
Set [Pr. 270 Stop-on contact/load torque high-speed frequency
control selection = 2 or 3].
When operating with the load torque high speed frequency
function
selection
signal
automatically changes the maximum frequency within the
setting range of [Pr. 4 Multi-speed setting (high speed)] and
[Pr. 5 Multi-speed setting (middle speed)] according to the
magnitude of the average current during the time to
accelerate from 1/2 of the frequency set in [Pr. 5] to the
frequency set in [Pr. 5].
When the average current of the current averaging range
(refer to A in the chart on the next page) during operation
with the X19 signal on is less than the "rated inverter
current" × [Pr. 271], the maximum frequency automatically
becomes the [Pr. 4] setting value.
When the average current of the current averaging time
period (refer to B in the chart on the next page) during
operation with the X19 signal on is higher than the "rated
inverter current" × [Pr. 272], the maximum frequency
automatically becomes the [Pr. 5] setting value.
During regeneration load operation, [Pr. 5] is the maximum
frequency regardless of the average current. When the
average current during acceleration is too small, it may be
judged as regeneration and the maximum frequency
becomes the setting of [Pr. 5].
The current averaging range can be set between 1/2
frequency of the [Pr. 273] setting value and [Pr. 273] set
frequency.
Initial
Setting
Value
Range
60Hz
0 to 400Hz Set the higher-speed frequency.
30Hz
0 to 400Hz Set the lower-speed frequency.
0
Normal operation
1
Stop-on-contact control (refer to page 396)
0
2
Load torque high speed frequency control
Stop-on-contact (refer to page 396) +load torque high speed frequency
3
control
50%
0 to 220%
Set the upper and lower limits of the current at high and middle speeds.
100%
0 to 220%
Average current during acceleration from ([Pr. 273]
0 to 400Hz
Hz can be achieved.
9999
Average current during acceleration from ([Pr. 5]
9999
is achieved.
Set the time constant of the primary delay filter relative to the output
16
1 to 4000
current. (The time constant [ms] is 0.75
12ms.) A larger setting provides higher stability but poorer response.
(X19)
ON,
the
inverter
starting to perform operation at higher than the preset
frequency under light load.
This function is designed to increase speed automatically
under light load, for example to minimize the incoming/
outgoing time in a multi-story parking lot.
Description
When the current averaging range includes the constant
power range, the output current may become large in the
constant power range.
When the average current value in the current averaging
range is small, deceleration time becomes longer as the
running frequency increases.
The maximum output frequency is 120Hz. The output
frequency is 120Hz even when the setting is above 120Hz.
Set [Pr. 178 to Pr. 189 (input terminal function selection) = 19]
and assign X19 signal function to the input terminal.
This control can be activated at every start. Fully note that
the speed changes every time if the magnitude of the load
differs every time.
It is valid in the External operation mode only, and restart
after instantaneous power failure function and fast-
response current limit function are invalid.
The load torque high speed frequency function is invalid in
the following operation conditions.
• PU operation ([Pr. 79])
• PU+external operation ([Pr. 79])
• JOG operation (JOG signal)
• PID control operation (X14 signal)
• Remote function selection operation ([Pr.59])
• Orientation control operation
• Multi-speed setting (RH, RM, and RL signals)
• 16bit digital input (FR-A7AX)
395
PARAMETER
A700
(A700)
1/2) Hz to ([Pr. 273])
1/2) Hz to ([Pr. 5] ) Hz
[Pr. 274] and the initial value is
2