Mitsubishi Electric FR-A700 Technical Manual page 527

Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

4.1.4
The inverter without magnetic contactor on the primary side
Related parameter
Reset selection, Pr. 75
*1
Set [Pr. 75 = 1] "Reset input is enabled only when the fault occurs" to disable resetting of the inverter during normal operation. (If
the inverter is reset during normal operation, the motor coasts to a stop. This setting is to prevent the inverter from resulting in
an alarm if the motor is still coasting when the inverter has returned from the reset status.)
*2
During operation, switch-over from "forward rotation" to "stop", then to "reverse rotation" is available.
In this case, when the reverse rotation signal is turned ON, the regenerative brake is applied down to the forward rotation
frequency of 0.5Hz, the opposite-phase brake is applied at or less than starting frequency and acceleration in reverse rotation is
started at that frequency. (DC injection brake is not applied.)
Change-over from forward
rotation to reverse rotation
Forward
rotation
Deceleration
*3
When making "forward rotation" to "reverse rotation" change-over during forward rotation in the above chart, change part of the
connection diagram as shown on the above.
*4
When an inverter with a regenerative brake resistor is used for cyclic or heavy duty operation, it is recommended to install a
magnetic contactor in the primary side to prevent the discharging resistor from overheat/burnout if the regenerative brake
transistor is damaged due to the thermal capacity shortage of the discharging resistor, and excessive regenerative brake duty,
etc.
*5
When the power supply is 400V class, install a step-down transformer.
MCCB
Power
supply
T
*5
F
Stop
Forward rotation
PB1
PB3
R
F
Reverse rotation
F
PB2
R
PB (Reset)
*1
Hz
Frequency meter
Moving-coil type 1mA
Frequency setting
potentiometer
2W1k
Time
Reverse rotation
Acceleration
Opposite-phase brake
Inverter
R
U
S
V
T
W
F
R
B
C
RES
SD
F
STF
R
STR
FM
10
(3)
2
(2)
(1)
5
Forward
Stop
rotation
PB3
PB1
F
R
561
PRACTICAL CIRCUITS
common
(common)
Motor
IM
Ground
Reverse
rotation
PB2
R
F
F
R
4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e700Fr-d700Fr-f700

Table of Contents