1.4.22 Maintenance timer alarm signal (Y95)
When the cumulative energization time of the inverter
reaches the parameter set time, the maintenance timer
output signal (Y95) is output.
operation panel (FR-DU07).
[Pr. ]
Name
503
Maintenance timer
Maintenance timer alarm
504
output set time
The cumulative energization time of the inverter is stored
into the EEPROM every hour and indicated in [Pr. 503
Maintenance timer] in 100h increments. [Pr. 503] is clamped
at 9998 (999800h).
When the [Pr. 503] setting reaches the time set in [Pr. 504
Maintenance timer alarm output set time] (100h increments),
the maintenance timer alarm output signal (Y95) is output.
For the terminal used for the Y95 signal output, assign the
function by setting 95 (positive logic) or 195 (negative
logic) in any of [Pr. 190 to Pr. 196 Output terminal function
selection].
*1
The cumulative energization time is counted every hour.
The energization time of less than 1h is not counted.
(MT) is displayed on the
Initial
Setting
Value
Range
0
0(1 to 9998)
0 to 9998
9999
9999
common
(common)
This can be used as a guideline for the maintenance time
of peripheral devices.
Displays the cumulative energization time of the inverter in
100h increments.
Reading only
Writing the setting of 0 clears the cumulative energization
time.
Set the time taken until when the maintenance timer alarm
output signal (Y95) is output.
No function
First power
ON
Maintenance
timer [Pr. 503]
9998
(999800h)
[Pr.504]
OFF
Y95 signal
MT display
74
SPECIFICATIONS
Description
ON
ON
Set "0" in [Pr.503]
Time