Specification List - Mitsubishi Electric FR-A700 Technical Manual

Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

(3) PWM
carrier
reduction function [Pr. 260]
When [Pr. 260 = 1 ] (initial value in
, performing continuous operation at
F700
D700
the 85% or more of the rated inverter current with the
inverter carrier frequency set to 3kHz or more ([Pr. 72
3]) will automatically reduce the carrier frequency
to 2kHz to protect the inverter output transistor.
(Although the motor acoustic noises increase, it is not
a fault.)
When [ Pr. 260 =0] (initial value in
, the carrier frequency is constant (at
F700
D700
the [ Pr.72 ] setting) regardless of the load, making
the motor sound uniform. For
operate continuously at less than 85% of the inverter
rated current when carrier frequency is set 3kHz or
more (less than the rated output current in
parenthesis on page 4) for keeping the carrier
frequency constant.
2.20.9 Cooling fan operation selection [Pr. 244]
The operation of built-in cooling fan (in forced cooling inverters) can be controlled. (To confirm which inverters are forced
cooling, refer to the specification list on page 2 .)
[Pr. ]
Name
Cooling fan operation
244
selection
In either of the following cases, fan operation is regarded
as faulty, [FN] is shown on the operation panel, and the fan
fault (FAN) and alarm (LF) signals are output.
• [When Pr. 244 = 0]
When the fan comes to a stop with power ON.
• When [Pr. 244 = 1]
When the inverter is running and the fan stops
during fan ON command.
frequency
automatic
F700
D700
) in
F700
) in
D700
, make sure to
F700
Initial Value
Setting Range
0
1
1
[When 55K or less]
14.5
Carrier
frequency
[kHz]
5
2
[When 75K or more]
6
Carrier
4
frequency
[Hz]
3
2
Carrier frequency automatic reduction
F700
D700
characteristics
common
(common
Operates in power-ON status.
Cooling fan ON/OFF control invalid (the cooling fan is always
on at power on)
Cooling fan ON/OFF control valid
The fan is always ON while the inverter is running. During a
stop, the inverter status is monitored and the fan switches ON-
OFF according to the temperature.
For the terminal used for FAN signal output, set 25
(positive logic) or 125 (negative logic) in any of [Pr. 190 to
Pr. 196 Output terminal function selection], and for the LF
signal, set 98 (positive logic) or 198 (negative logic).
431
PARAMETER
When
[Pr. 72 = 5]
85%
100%
Current
When
[Pr. 72 = 3]
85% 100%
Current
)