<Set point input calibration>
1) Apply the input voltage of 0% set point setting (e.g.
0V) across terminals 2-5.
2) Enter in [C2 (Pr. 902)] the frequency which should be
output by the inverter at the deviation of 0% (e.g.
0Hz).
3) In [C3 (Pr. 902)], set the voltage value at 0%.
4) Apply the voltage of 100% set point (e.g. 5V) across
terminals 2-5.
5) Enter in [Pr. 125] the frequency which should be
output by the inverter at the deviation of 100% (e.g.
60Hz).
6) In [C4 (Pr. 903)], set the voltage value at 100%.
<Detector output calibration>
1) Apply the output current of 0% detector setting (e.g.
4mA) across terminals 4-5.
2) Make calibration using [C6 (Pr. 904)].
3) Apply the output current of 100% detector setting
(e.g. 20mA) across terminals 4-5.
4) Make calibration using [C7 (Pr. 905)] .
5) The frequency set in [C5 (Pr. 904)] and [Pr. 126]
should be the same as set in [C2 (Pr. 902)] and [Pr.
125].
The results of the above calibration are as shown below:
[Set point setting]
(%)
100
0
0
[Detection value]
(%)
100
0
0
4
[Manipulated value]
60
0
0
(V)
5
20
(mA)
100 Deviation(%)
410
PARAMETER