Type FR-A740-
K
Applicable motor capacity
(kW)
*1
Rated capacity (kVA)
*2
Rated current (A)
*3
Overload current rating
*4
Voltage
*5
Regenerative
Maximum value/
braking torque
permissible duty
Rated input AC voltage/
frequency
Permissible AC voltage
fluctuation
Permissible frequency
fluctuation
Power supply
Without DC
system
reactor
capacity
With DC
(kVA)
reactor
*7
Protective structure (JEM
1030)
*9
Cooling system
Approximate mass (kg)
*1
The applied motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
*2
The rated output capacity indicated assumes that the output voltage is 220V for 200V class and 440V for 400V class.
*3
When operating the inverter of 75K or more with a value larger than 2kHz set in [Pr. 72 PWM frequency selection], the rated output
current is the value in parenthesis.
*4
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For
repeated duty, allow time for the inverter and motor to return to or below the temperatures under 100% load.
*5
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within
the setting range. However, the pulse voltage value of the inverter output side voltage remains unchanged at about
the power supply.
*6
200V: When FR-ABR (option) is connected, 150% torque 10% ED for 0.4K and 0.75K, 100% torque 10%ED for 1.5K to 7.5K,
100% torque 6%ED for 11K to 22K.
400V: When FR-ABR-H (option) is connected, 15% torque 10% ED for 0.4K to 7.5K, 100% torque 6% ED for 11K to 22K.
*7
The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input
reactor and cables).
*8
When the hook of the inverter front cover is cut off for installation of the plug-in option, protective structure of the inverter
changes to an open type (IP00).
*9
FR-DU07 : IP40 (except for the PU connector)
75
90
110
132
160
75
90
110
132
160
110
137
165
198
248
144
180
216
260
325
(122)
(153)
(184)
(221)
(276)
150% 60s, 200% 3s (inverse-time characteristics) surrounding air temperature 50
110
137
165
198
248
50
57
72
72
110
185
220
250
280
185
220
250
280
275
329
367
417
361
432
481
547
(307)
(367)
(409)
(465)
Three-phase 380 to 480V
10% torque/continuous
Three-phase 380 to 480V 50Hz/60Hz
323 to 528V 50Hz/60Hz
±5%
275
329
367
417
Open type (IP00)
Forced air cooling
110
175
175
175
3
SPECIFICATIONS
315
355
400
450
500
315
355
400
450
500
465
521
587
660
733
610
683
770
866
962
(519)
(581)
(655)
(736)
(818)
465
521
587
660
733
260
260
370
370
370
that of