(d) Calculation of outgoing harmonic current of
each degree
Outgoing harmonic current
= Rated current converted from received power
voltage
maximum operation ratio
harmonic content
Note that the harmonic content is as
indicated in the table on the next page.
(If the consumer has a facility to reduce
harmonic currents, its effect may be taken
into consideration.)
Fundamental wave currents and rated capacities of
inverters
Motor
Fundamental Wave
Capacity
Current [A]
[kW]
200V
400V
0.4
1.61
0.81
0.75
2.74
1.37
1.5
5.50
2.75
2.2
7.93
3.96
3.7
13.0
6.5
5.5
19.1
9.55
7.5
25.6
12.8
11
36.9
18.5
15
49.8
24.9
18.5
61.4
30.7
22
73.1
36.6
30
98.0
49.0
37
121
60.4
45
147
73.5
55
180
89.9
75
245
123
90
293
147
110
357
179
132
216
160
258
220
355
250
403
280
450
315
506
355
571
400
643
450
723
500
804
560
900
3
10
[mA]
Rated Capacity
[kVA]
200V
400V
0.57
0.97
1.95
2.81
4.61
6.77
9.07
13.1
17.6
21.8
25.9
34.7
42.8
52.1
63.7
87.2
104
127
153
183
252
286
319
359
405
456
512
570
638
511