(7) Switching of operation mode by external
signal (X16 signal)
When external operation and operation from the
operation panel are used together, use of the PU-
external operation switching signal (X16) allows
switching between the PU operation mode and
External operation mode during a stop (during a
motor stop, start command OFF).
When [Pr. 79 = 0, 6, 7] , the operation mode can be
switched between the PU operation mode and
[Pr. 79]
X16 Signal State Operation Mode
ON (External)
Setting
0(initial value) External operation mode
1
2
3, 4
External/PU combined operation mode
6
External operation mode
X12(MRS)
External operation mode
ON
7
X12(MRS)
OFF
OFF (PU)
PU operation mode
PU operation mode
External operation mode
PU operation mode
PU operation mode
External operation mode
External operation mode. ([Pr. 79 = 6] At switch-over
mode, operation mode can be changed during
operation)
For the terminal used for X16 signal input, set 16 in
any of [Pr. 178 to 189 input terminal function selection]
to assign the function.
Can be switched to External, PU or NET operation mode
Fixed to PU operation mode
Fixed to External operation mode (can be switched to NET
operation mode)
Fixed to External/PU combined mode
Switching among the External, PU, and NET operation mode is
enabled while running.
Can be switched to External, PU or NET operation mode
(Output stop in External operation mode)
Fixed to External operation mode (forcibly switched to External
operation mode)
213
PARAMETER
Remarks
2