Mitsubishi Electric FR-A700 Technical Manual page 45

Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Using [Pr. 178 to Pr. 189], set the functions of the input terminals.
Refer to the following table and set the parameters :
Setting
Signal
[Pr. 59 = 0] (initial value)
[Pr. 59 ≠ 0]
0
RL
[Pr. 270 = 1, 3]
[Pr. 59 = 0] (initial value)
1
RM
[Pr. 59 ≠ 0]
[Pr. 59 = 0] (initial value)
2
RH
[Pr. 59 ≠ 0]
Second function selection
3
RT
[Pr. 270 = 1, 3]
4
AU
Terminal 4 input selection
5
JOG
Jog operation selection
Selection of automatic restart after instantaneous power failure, flying
start
6
CS
Commercial power supply-inverter switchover function
7
OH
External thermal relay input
8
REX
15-speed selection (combination with three speeds RL, RM, RH)
9
X9
Third function selection
10
X10
Inverter run enable signal (FR-HC, MT-HC/FR-CV connection)
11
X11
FR-HC, MT-HC connection, instantaneous power failure detection
12
X12
PU operation external interlock
13
X13
External DC injection brake operation start
14
X14
PID control valid terminal
15
BRI
Brake opening completion signal
16
X16
PU-external operation switchover
17
X17
Load pattern selection forward rotation reverse rotation boost
18
X18
V/F switchover (V/F control is exercised when X18 is ON)
19
X19
Load torque high-speed frequency
20
X20
S-pattern acceleration/deceleration C switchover
22
X22
Orientation command
23
LX
Pre-excitation/servo ON
Output stop
24
MRS
Commercial power supply-inverter switchover function
25
STOP
Start self-holding selection
26
MC
Control mode switchover
27
TL
Torque limit selection
28
X28
Start-time tuning start external input
42
X42
Torque bias selection1
43
X43
Torque bias selection2
44
X44
P/PI control switchover
60
STF
Forward rotation (assigned to STF terminal [Pr. 178] only)
61
STR
Reverse rotation (assigned to STR terminal [Pr. 179] only)
62
RES
Inverter reset
63
PTC
PTC thermistor input (assigned to AU terminal ([Pr. 184]) only)
64
X64
PID forward/reverse action switchover
65
X65
PU/NET operation switchover
66
X66
External/NET operation switchover
67
X67
Command source switchover
68
NP
Conditional position pulse train sign
69
CLR
Conditional position droop pulse clear
70
X70
DC feeding operation permission
Functions
Low-speed operation command
Remote setting (setting clear)
*1
Stop-on contact selection 0
*2
Middle-speed operation command
Remote setting (deceleration)
*1
High-speed operation command
Remote setting (acceleration)
*1
Stop-on contact selection 1
*2
*3
*4 *6
*5
*6
*6
*6
*6
38
SPECIFICATIONS
Available Inverters
A700
F700
E700
D700

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e700Fr-d700Fr-f700

Table of Contents