Motor
Applied
Output
Inverter
(kW)
Type
*1
0.4
FR-A740-0.4K
0.75
FR-A740-0.75K 30AF 5A
1.5
FR-A740-1.5K
2.2
FR-A740-2.2K
3.7
FR-A740-3.7K
5.5
FR-A740-5.5K
7.5
FR-A740-7.5K
11
FR-A740-11K
15
FR-A740-15K
18.5
FR-A740-18.5K 100AF 75A
22
FR-A740-22K
30
FR-A740-30K
37
FR-A740-37K
45
FR-A740-45K
55
FR-A740-55K
75
FR-A740-75K
90
FR-A740-90K
110
FR-A740-110K
132
FR-A740-132K
150
FR-A740-160K
160
FR-A740-160K
185
FR-A740-185K
220
FR-A740-220K
250
FR-A740-250K
280
FR-A740-280K
315
FR-A740-315K
355
FR-A740-355K
400
FR-A740-400K
450
FR-A740-450K
500
FR-A740-500K
*1
Selections for use of the Mitsubishi 4-pole standard
motor with power supply voltage 200VAC (200V class)/
400VAC (400V class) 50Hz.
*2
Install one MCCB per inverter.
For the use in the United States or Canada, provide the
appropriate UL and cUL listed Class RK5, Class T or
Class L type fuse or UL489 molded case circuit breaker
(MCCB) that is suitable for branch circuit protection. For
details, refer to page 552.
MCCB
INV
IM
MCCB
INV
IM
*3
Magnetic contactor is selected based on the AC-1 class.
The electrical durability of magnetic contactor is 500,000
times. When the magnetic contactor is used for
emergency stop during motor driving, the electrical
durability is 25 times.
Peripheral device selection list (example
Moulded Case Circuit Breaker (MCCB)
or Earth Leakage Circuit Breaker (ELB)
Reactor connection
Without
30AF 5A
30AF 5A
30AF 5A
30AF 10A
30AF 10A
30AF 10A
30AF 10A
30AF 20A
30AF 15A
30AF 30A
30AF 20A
30AF 30A
30AF 30A
50AF 50A
50AF 40A
100AF 60A
50AF 50A
100AF 60A
100AF 100A
100AF 75A
225AF 125A
100AF 100A
225AF 150A
225AF 125A
225AF 175A
225AF 150A
225AF 200A
225AF 175A
225AF 225A
225AF 225A
225AF 225A
400AF 400A
400AF 400A
400AF 400A
400AF 400A
600AF 500A
600AF 600A
600AF 600A
800AF 700A
800AF 800A
1000AF 900A
1000AF 1000A
1200AF 1200A
)
A700
Magnetic contactor on
*2
Reactor connection
With
Without
S-N10
S-N10
S-N10
S-N10
S-N10
S-N20,
S-N20,
S-N20,
S-N25
S-N25
S-N35
S-N50
S-N65
S-N80
S-N80
When using the MC for emergency stop during motor
driving or using on the motor side during commercial-
power supply operation, select the class AC-3 rated
current for the motor rated current.
*4
Cable
For the 55K or less, the recommended cable size is the
cable (HIV cable (600V class 2 vinyl-insulated cable)
etc.) with continuous maximum permissible temperature
of 75°C. Assumes that the surrounding air temperature is
50°C or less and the wiring distance is 20m or less.
For the 75K or more, the recommended cable size is the
cable (e.g. LMFC (heat resistant flexible cross-linked
polyethylene insulated cable)) with continuous maximum
permissible temperature of 90°C.
surrounding air temperature is 50°C or less and wiring is
performed in an enclosure.
527
SELECTION
Recommended
Cable Size
the Input Side
*3
(mm
R, S, T U, V, W
With
S-N10
2
S-N10
2
S-N10
2
S-N10
2
S-N10
2
S-N11,
2
N21
N12
S-N20,
3.5
N21
N21
S-N20,
5.5
N21
N21
S-N20,
8
N21
S-N25
14
S-N25
14
S-N50
22
S-N50
22
S-N65
38
S-N80
60
S-N95
60
S-N150
60
S-N180
80
S-N220
100
S-N300
125
S-N300
125
S-N300
150
2 × 100
S-N400
2 × 100
S-N600
2 × 125
S-N600
2 × 150
S-N600
2 × 200
S-N600
2 × 200
S-N800
1000A
2 × 250
rated
product
1000A
3 × 200
rated
product
Assumes that the
2
)
*4
2
2
2
2
2
2
3.5
5.5
8
8
14
22
22
38
60
60
60
80
100
150
150
150
2 × 100
2 × 100
2 × 125
3
2 × 150
2 × 200
2 × 200
2 × 250
2 × 250