(4) If the MC in the main circuit power is switched OFF, the
fault output signal is not switched ON. When the MC is
OFF, the operation panel and parameter unit (FR-
DU07, FR-PU07) can be operated. (The motor cannot
be run)
1.4.3
Switching the inverter output MC ON/OFF (U, V, W)
Switch the magnetic contactor between the inverter and
motor only when both the inverter and motor are at a stop.
When the magnetic contactor is turned ON while the
inverter is operating, overcurrent protection of the inverter
(1) When inverter output MC switch-ON
Motor State before
Inverter State
Inverter operating
Inverter at stop
*1
MC switch-ON might become available by selecting an appropriate inverter capacity. (For example, select an inverter capacity
considering the start current of the motor. Refer to page 476.)
*2
Because overcurrent protection and electronic thermal protection may occur at an inverter start, use of automatic restart after
instantaneous power failure/flying start (refer to page 367) is recommended.
(2) When inverter output MC switch-OFF
Motor State before
Inverter State
Inverter operating
Inverter at stop
1.4.4
Input signal (STF, STR, RL, RM, RH, RT, AU, JOG, CS, MRS, STOP, RES)
(1) Input terminal function assignment
Use these parameters to select/change the input terminal functions.
1)
A700
F700
[Pr.]
Name
STF terminal function
178
selection
STR terminal function
179
selection
RL terminal function
180
selection
RM terminal function
181
selection
RH terminal function
182
selection
RT terminal function
183
selection
AU terminal function
184
selection
JOG terminal function
185
selection
CS terminal function
186
selection
MRS terminal function
187
selection
STOP terminal function
188
selection
RES terminal function
189
selection
common
Power on
Motor Running (Coasting)
MC may not be switched ON
MC may not be switched ON
common
Power on
Motor Running
MC may be switched OFF
(The motor coasts to a stop)
common
2)
E700
Initial
[Pr.]
Name
Value
STF terminal function
60
178
selection
STR terminal function
61
179
selection
RL terminal function
0
180
selection
RM terminal function
1
181
selection
RH terminal function
2
182
selection
MRS terminal function
3
183
selection
RES terminal function
4
184
selection
5
6
24
25
62
(5) Capacity (VA) of separate power supply
The following power capacity is necessary when
separate power is supplied from R1/L11 and S1/L21.
FR-A720-11K or less, FR-A740-15K or less...60VA or more
FR-A720-15K or more, FR-A740-18.5K or more...80VA or
more
FR-F720-15K or less, FR-F740-18.5K or less...60VA or more
FR-F720-18.5K or more, FR-F740-22K or more...80VA or
more
common
(common
and such will activate. When an MC is provided to switch to
a
commercial
power
recommended to use bypass-inverter switchover function
[Pr. 135 to Pr. 139] (refer to page 416).
Motor Running
(Coasting)
MC may be switched OFF
3)
Initial
[Pr.]
Value
60
178
61
179
0
180
1
181
2
182
24
62
37
SPECIFICATIONS
)
supply,
for
example,
Motor at Stop
MC may not be switched ON
MC may be switched ON
Motor at Stop
MC may be switched OFF
common
(common
D700
Name
STF terminal function
selection
STR terminal function
selection
RL terminal function
selection
RM terminal function
selection
RH terminal function
selection
it
is
1
)
Initial
Value
60
61
0
1
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e700Fr-d700Fr-f700

Table of Contents