Mitsubishi Electric FR-A700 Technical Manual page 84

Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

1.4.24 Remote output function (REM)
[Pr. ]
Name
Remote output
495
selection
496
Remote output data 1
497
Remote output data 2
You can utilize the ON/OFF of the inverter's output signals
instead of the remote output terminal of the programmable
controller.
The output terminal can be turned ON/OFF depending on
the [Pr. 496 or Pr. 497] setting. The remote output selection
can
be
controlled
ON/OFF
communication from the PU connector or RS-485 terminal
or by communication from the communication option.
Set 96 (positive logic) or 196 (negative logic) in any of [Pr.
190 to Pr. 196 Output terminal function selection], and assign
the remote output (REM) signal to the terminal used for
remote output.
When you refer to the following diagram and set 1 to the
terminal bit (terminal where the REM signal has been
assigned) of [Pr. 496 or Pr. 497], the output terminal turns
ON (OFF for negative logic). By setting 0, the output
terminal turns OFF (ON for negative logic).
The output terminal where the REM signal is not assigned
using any of [Pr. 190 to Pr. 196] does not turn ON/OFF if 0/1
is set to the terminal bit of [Pr. 496, Pr. 497]. (It turns ON/
OFF with the assigned function.)
For example when [Pr. 190 RUN terminal function selection =
96] (positive logic) and set 1 (H01) in [Pr. 496], the terminal
RUN turns ON.
When [Pr. 495 = 0, 10], performing a power ON reset
(including a power failure) clears the REM signal output.
(The ON/OFF status of the terminals are as set in [Pr. 190
to Pr. 196]. ) The [Pr. 496, 497] settings are also 0.
When [Pr. 495 = 1, 11], the remote output data before
power OFF is stored into the EEPROM, so the signal
output at power recovery is the same as before power OFF.
However, it is not stored into EEPROM when the inverter is
reset
(terminal
reset,
communication). (Refer to the following diagram)
When [Pr. 495 = 10, 11], signal before reset is saved even
at inverter reset.
(common)
Initial
Setting
Value
Range
0
Remote output data clear at powering OFF
Remote output data retention even at
1
powering OFF
0
10
Remote output data clear at powering OFF
Remote output data retention even at
11
powering OFF
0
0 to 4095
Refer to the following diagram.
0
0 to 4095
by
computer
link
reset
request
through
common
Description
[Pr. 495 = 0, 10]
Power
OFF
supply
OFF REM
REM
REM signal clear
ON/OFF example for positive logic
*1
When [Pr. 495 = 1, 11] (remote output data retention even
at powering OFF), take such corrective action as
connection of R1/L11, S1/L21 and P/
control power supply. If you do not take such a step, the
output signals provided after power-ON are not
guaranteed.
<Remote output data>
1)
A700
F700
[Pr. 496]
b11
[Pr. 497]
b11
*1
As desired
*2
Terminal Y0 to Y6 are available only when the
extension output option (FR-A7AY) is fitted
*3
Terminal RA1 to RA3 are available only when the
relay output option (FR-A7AR) is fitted
77
SPECIFICATIONS
Available
Inverters
A700
F700
D700
E700
Remote output
data clear at
inverter reset
Remote output
data retention at
inverter reset
[Pr. 495 = 1, 11]
Power
OFF
supply
Inverter
reset time
(about 1s)
ON
REM signal held
-
, N/
, to hold the
+
1
b0
b0