4.15 Reversible operation by analog input
A700 F700
By changing the polarity of the analog input signal to terminal 1 between positive and negative, reversible operation can be
performed between forward rotation and reverse rotation.
MCCB
Power
supply
Ready
"ON"
"OFF"
PB1
PB2
MC
Stop
Run
PB4
MC
PB3
F
Frequency
setting device
( power supply)
*1
This magnetic contactor is provided to prevent an automatic restart when power is restored after a power failure. Use the start
signal (ON or OFF of STF) to make a start or stop.
*2
When the power supply is 400V class, install a step-down transformer.
*3
Set [Pr. 75 = 1] "Reset can be made only when a fault occurs" to disable resetting the inverter during normal operation.
(If the inverter is reset during normal operation, the motor coasts to a stop. This setting is made to prevent the inverter from
resulting in an alarm if the motor is still coasting when the inverter has returned from the reset status.)
Inverter
MC
*1
R
S
T
T
*2
F
C
M
B
C
F
1
5
Hz
FM
Frequency meter
Moving-coil type
1mA
SD
F
STF
583
PRACTICAL CIRCUITS
U
Motor
V
IM
W
Earth (Ground)
Frequency
Reverse
rotation
5V
0
-
(10V)
Frequency setting input
Use [Pr. 73] to choose the voltages
within parentheses.
Reset
PB6
RES
SD
Related parameters
Reset selection/disconnected PU detection
/PU stop selection [Pr. 75]
Analog input selection [Pr. 73]
(A700, F700)
Forward
rotation
5V
+
(10V)
4