Vector control [Pr. 71, 80, 81, 359, 369, 800]
This method divides the currents flowing in the motor into a
current for making a magnetic flux in the motor and a
current for causing the motor to develop a torque and
controls each current separately. Therefore, very high
response is obtained and torque at low speed can be
generated stably.
Initial
[Pr. ]
Name
Value
71
Applied motor
80
Motor capacity
Number of motor
81
poles
Encoder rotation
359
direction
Number of encoder
369
pulses
Control method
800
selection
* Use [Pr. 178 to Pr. 189] to assign the terminals used for the X18 and MC signal.
** When [Pr. 80 Motor capacity = 9999] or [Pr. 81 Number of motor poles = 9999], control method is V/F control regardless of the [Pr. 800] setting.
(1) Conditions of vector control selection
Vector control may only be utilized effectively when
all of the following conditions are satisfied.
If any of the conditions cannot be satisfied, torque
shortage, speed fluctuation or another fault may have
occurred. Operate under V/F control in that case.
A plug-in option FR-A7AP or FR-A7AL should be
fitted to the inverter.
The encoder should be coupled on the same
axis with the motor shaft without any mechanical
looseness. The speed ratio should be 1:1.
When the standard motor or constant motor is
used, the motor capacity should be equal to or
one rank lower than the inverter capacity.
Note that the motor capacity should be 0.4kW or
more.
Setting Range
0 to 8, 13 to 18, 20, 23, 24, 30,
0
33, 34, 40, 43, 44, 50, 53, 54
55K or less
0.4 to 55kW
9999
75K or more
0 to 3600kW
9999
2, 4, 6, 8, 10
9999
12, 14, 16, 18, 20
9999
0
1
1
1024
0 to 4096
0 to 5
9
20
10, 11, 12
20
A700
(A700)
It is necessary to know the motor speed to perform this
control, and a motor with an encoder and a plug-in option
FR-A7AP or FR-A7AL are required.
It responds to the load variation quickly (high response) by
torque current control, and torque control is also enabled
by giving torque command.
It has excellent control characteristics and achieves the
control characteristics equal to those of DC machines.
Description
By selecting a standard motor or constant torque motor, thermal
characteristic and motor constants of each motor are set.
Set the applied motor capacity.
V/F control
Set the number of motor poles.
X18 signal-ON:
Set 10 + number of motor poles .
V/F control *
V/F control
A
Encoder
Clockwise direction as viewed
from A is forward rotation
CCW
A
Encoder
Counter clockwise direction as
viewed from A is forward rotation
Set the number of pulses of the encoder.
Set the number of pulses before multiplied by four.
Vector control
Vector control test operation
V/F control **
Real sensorless vector control
Advanced magnetic flux vector control
For the vector control dedicated motor, the
inverter one or two ranks higher than the motor
in capacity needs to be selected depending on
the motor capacity. Refer to the table on the next
page for combination with a vector control
dedicated motor.
The motor type is the Mitsubishi standard motor
with an encoder, Mitsubishi high efficiency motor
(SF-JR, SF-HR 2 poles, 4 poles, 6 poles 0.4kW
or more) or Mitsubishi constant torque motor
(SF-JRCA 4 poles, SF-HRCA 0.4kW to 55kW),
or vector control dedicated motor (SF-V5RU).
When any other motor (other manufacturer
standard motor, other manufacturer constant
torque motor) is used, use this function after
performing offline auto tuning (refer to page268)
without fail .
Single-motor operation (one motor run by one
inverter) should be performed.
Wiring length from inverter to motor should be
within 30m. If the length is over 30m, perform
offline auto tuning with the cables wired.
263
PARAMETER