When the set frequency (speed) is 100 or more,
frequency is displayed in 0.1 increments. Therefore,
the minimum varying width is 0.1 even when [Pr. 295
<0.1].
When the set frequency (speed) is 1000 or more,
frequency is displayed in 1 increments. Therefore,
the minimum varying width is 1 even when [Pr.
295<1].
(5) Buzzer control [Pr. 990]
You can select to make the buzzer "beep" when you
press key of the operation panel and parameter unit
(FR-PU04/FR-PU07) or not by using [Pr. 990].
2.18.8 Setting an operation panel (PA02) for FR-E500 series
Operation panel for the FR-E500 series (PA02) can be used by connecting with PU cable.
(PA02 cannot be connected to the inverter body directly.)
[ Pr. ]
146
Built-in potentiometer switching
Frequency setting voltage bias
C22(922)
frequency (built-in potentiometer)
Frequency setting voltage bias (built-
C23(922)
in potentiometer)
Frequency setting voltage gain
C24(923)
frequency (built-in potentiometer)
Frequency setting voltage gain (built-
C25(923)
in potentiometer)
(1) Built-in potentiometer switching [Pr. 146]
Switches the frequency setting method between the
PA02 built-in frequency setting potentiometer and
digital frequency setting by the
Set [Pr.146 =0] only when operating by a built-in
frequency setting potentiometer of an operation
panel for the FR-500 series (PA02). When [Pr.146
=0], operation may not be available from an inverter's
operation panel or by communication.
(2) Bias and gain of the built-in frequency
setting potentiometer [C22 (Pr. 922) to C25
(Pr. 923)]
When the operation panel (PA02) for the FR-E500
series is hooked up with the PU cable, the magnitude
(slope) of the output frequency to the frequency
Initial
Name
Value
1
0Hz
0%
60Hz
100%
key.
(6) PU contrast adjustment [Pr. 991]
The LCD contrast of the parameter unit (FR-PU04/
FR-PU07) can be adjusted using [Pr. 991].
Decreasing the setting value makes contrast light.
The contrast can be adjusted by changing the setting
with
At this time, press
Setting
Range
PA02 built-in frequency setting potentiometer valid
0
Frequency setting by the built-in frequency setting
potentiometer
PA02 built-in frequency setting potentiometer invalid
Digital frequency setting by the
Changing frequency continuously by pressing the
1
The value changes while pressing down the
Frequency on the bias side of PA02 built-in frequency
0 to 400Hz
setting potentiometer.
Converted % of the bias side setting level of PA02 built-
0 to 300%
in frequency setting potentiometer.
Frequency on the gain side of PA02 built-in frequency
0 to 400Hz
setting potentiometer.
Converted % of the bias side setting level of PA02 built-
0 to 300%
in frequency setting potentiometer.
setting potentiometer of the operation panel can be
set as desired.
Adjust the bias of the potentiometer of the operation
panel using [Pr. 922 (C22, C23)] and gain with [Pr. 923
(C24, C25)].
60Hz
Bias
C22 (Pr. 922)
0
C23 (Pr. 922)
Frequency setting signal
(Built-in frequency setting potentiometer)
390
PARAMETER
of the parameter unit.
to store the setting.
WRITE
E700 D700
(E700)(D700)
Description
key.
key.
Initial value
100%
C25 (Pr. 923)
key.
Gain
C24 (Pr. 923)