1.4.11 Second function selection signal, third function selection signal (RT, X9
common
(common
Second (third) function can be selected with the RT (X9)
signal.
When the RT signal turns ON, the second function
becomes valid.
When the X9 signal turns ON, the third function becomes
valid.
For RT signal, set "3" to any of [ Pr.178 to 189 Input terminal
function selection ] to assign the function. For X9 signal, set
"9" to any of [ Pr.178 to 189 Input terminal function selection ]
to assign the function.
[Pr.]
Name
RT signal function
155
validity condition
selection
Start
Second
function
selection
High speed
Middle speed
Second function connection diagram
)
Initial
Setting
Value
Range
0
0
10
Inverter
STF (STR)
RT
RH
RM
SD
(*X9 is not available for the
The second (third) function has the following applications.
1) Switching between normal use and emergency
use
2) Switching between heavy load and light load
3) Changing of acceleration/deceleration time by
broken line acceleration/deceleration
4) Switching of characteristic between the main
motor and sub motor
You can set the operating condition (reflection timing) for
second (third) function with [Pr.155] in
The function immediately activates by turning ON/OFF the
RT signal in
E700
Description
Second (third) function is immediately made
valid with ON of the RT (X9) signal.
Second (third) function is valid only during the
RT (X9) signal is ON and constant speed
operation. (invalid during acceleration/
deceleration)
[Pr.155= 0]
RT
RH
RM
Second acceleration/deceleration time example
54
SPECIFICATIONS
F700
E700
A700
F700
.
D700
Setting Range
A700
F700
(initial value)
Acceleration
time is reflected
Time
*
)
.)
D700
.
E700
D700