5.10 Selecting control mode

 : V/F control mode selection
• Function
With VF-FS1, the V/F controls shown below can be selected.
V/F constant
Variable torque
Automatic torque boost control
Vector control
Advanced energy saving
PM motor control
[Parameter setting]
Title
5

Steps in setting are as follows
(In this example, the V/F control mode selection parameter  is set to  (Vector control).
Setting V/F control mode selection to 3 (sensorless vector control)
Key operated
Function
V/F control mode selection
LED display
.
MODE


ENT
ENT
⇔ 
Adjustment range
0: V/F constant
1: Variable torque
2: Automatic torque boost control
3: Vector control
4: Advanced energy-saving
5: - (Do not select)
6: PM motor control
Operation
Displays the operation frequency. (Perform during operation stopped.)
(When standard monitor display selection  is set to 
[Operation frequency])
The first basic parameter "" (Wizard function) is displayed.
Press the
key to change the parameter to  (V/F control mode
selection).
Press the ENT key to display the parameter setting. (Standard
default setting:  ( Variable torque)).
Press the
key to change the parameter to  (vector control).
Press the ENT key to save the changed parameter.  and
parameter set value "" are displayed alternately.
E-18
E6581381
Default setting
1