Display Of Detailed Information On A Past Trip - Toshiba TOSVERT VF-FS1 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-FS1:
Table of Contents

Advertisement

8.1.2
Details on a past trip (of trips 1 to 4) can be displayed, as shown in the table below, by pressing the
when the trip record is selected in the status monitor mode.
Unlike the "Display of detailed trip information at the occurrence of a trip" in 8.2.2, details on a past trip can be
displayed, even after the inverter is turned off or reset.
Item displayed
Note 10
Past trip 1
Continuous trips
Operation
Note 1
frequency
Direction of
rotation
Operation
frequency
command
Note 2
Load current
Note 3
Input voltage
Output voltage
8
Input terminal
Note 4
Output terminal
Note 5
Cumulative
operation time
Note 8
Past trip 1

Display of detailed information on a past trip

Key
LED display
operated
⇔
ENT










⇔
MODE
Past trip 1 (displayed alternately)
The number of time the same trip occurred in succession is
displayed. (Unit: times)
The operation frequency when the trip occurred is
displayed.
The direction of rotation when the trip occurred is displayed.
(: Forward run, : Reverse run)
The operation command value when the trip occurred is
displayed.
The inverter output current when the trip occurred is
displayed. (%/A)
The inverter input voltage (DC detection) when the trip
occurred is displayed. (%/V).
The inverter output voltage when the trip occurred is
displayed. (%/V)
The ON/OFF statuses of the control input terminals (F, R,
RES and VIA) are displayed in bits.
ON: 

OFF: 
VIA
The ON/OFF statuses of the control output terminals (RY
and FL) are displayed in bits.
ON: 
OFF: 
The cumulative operation time when the trip occurred is
displayed.
(0.01=1 hour, 1.00=100 hours)
Press this key to return to past trip 1.
H-4
E6581381
key
ENT
Description
 
F
R
RES

FL
RY-RC

Advertisement