Example of how to adjustment the FM terminal frequency meter
*
Use the meter's adjustment screw to pre-adjust zero-point.
Key operated
MODE
5
MODE
Adjusting the meter in inverter stop state
• Adjustment of output current (=)
If, when adjusting the meter for output current, there are large fluctuations in data during adjustment,
making adjustment difficult, the meter can be adjusted in inverter stop state.
When setting  to  for fixed output 1 (100% output current), a signal of absolute values will be
output (inverter's rated current = 100%). In this state, adjust the meter with the  (Meter adjustment)
parameter.
Similarly, if you set  to  for fixed output 2 (output current at 50%), a signal that is sent out when
half the inverter's rated current is flowing will be output through the FM terminal.
After meter adjustment is ended, set  to  (output current).
• Adjustment of other items (=,  to , )
If parameter  is set to : Fixed output 3 (Other than the output current: 100%), a signal that is
sent out when  is set to ,  to , (100%) will be output through the FM terminal.
100% standard value for each item is the following:
LED display
-
. 


. 
ENT
. 
 ⇔ 
ENT
+
MODE
. 
: Maximum frequency ()
=, , 
: 1.5 times of rated voltage
=, 
: 1.85 times of rated power
=, 
=, 
: 2.5 times of rated torque
=, 
: Rated load factor
: Maximum input value
=, 
: FA51=1000
=
Displays the operation frequency.
(When standard monitor display selection  is set to  [Operation
frequency])
The first basic parameter "" (Wizard function) is displayed.
Press either the
or the
key to select "".
Press the ENT key to display the operation frequency
Press either the
key or the
The meter reading will change at this time but be careful because there
will be no change in the inverter's digital LED (monitor) indication.
The adjustment is complete.  and the frequency are displayed
alternately.
The display returns to its original indications.
(When standard monitor display selection  is set to  [Operation
frequency])
E-12
Operation
key to adjust the meter.
[Hint]
It's easier to make the adjustment if you
push and hold for several seconds.
E6581381