[Parameter setting]
Title
 VIA input point 1 setting
 VIA input point 1 frequency
 VIA input point 2 setting
 VIA input point 2 frequency
 VIB input point 1 setting
 VIB input point 1 frequency
 VIB input point 2 setting
 VIB input point 2 frequency
 Communication command point 1 setting
 Communication command point 1 frequency
 Communication command point 2 setting
 Communication command point 2 frequency
Note: Don't set the same value between point 1 and point 2. If set the same falue, the  is displayed.
1) 0-10Vdc voltage input adjustment (VIA, VIB)
VIA, VIB terminals
/
Output
frequency
/
2) 4-20mAdc current input adjustment (VIA: VIA (SW3) slide switch in the I position)
VIA terminal
Output
frequency
Function
60 ( Hz )
0 ( Hz)
/
/
0 (%)
100 (%)
0
10V voltage signal
Frequency commnd

60 ( Hz )

0 ( Hz)


20 (%)
100 (%)
4
20mA current signal
Frequency commnd
F-19
Adjustment range
Default setting
0-100 (%)
0.0-200.0 (Hz)
0-100 (%)
50.0 (WP type)
0.0-200.0 (Hz)
60.0 (WN type)
0-100 (%)
0.0-200.0 (Hz)
0-100 (%)
50.0 (WP type)
0.0-200.0 (Hz)
60.0 (WN type)
0-100 (%)
0.0-200.0 (Hz)
0-100 (%)
50.0 (WP type)
0.0-200.0 (Hz)
60.0 (WN type)
・The output frequency with
respect to the voltage input is
adjusted according to the
selected reference point.
・Gradient and bias can be set
easily.
・The output frequency with respect to
the current input is adjusted
according to the selected reference
point.
・Gradient and bias can be set easily.
・Set  to  to create a current
input from 0 to 20mA.
E6581381
0
0.0
100
0
0.0
100
0
0.0
100
6