Toshiba TOSVERT VF-FS1 Instruction Manual page 155

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-FS1:
Table of Contents

Advertisement

Title
Small current detection current hysteresis

Small current trip/alarm selection

Small current detection current

Small current detection time

<Example of operation>
Output terminal function: 24 (UC) Low current detection
 =  (Alarm only)
Low current
signal output
Output current (%)
 + 

*
When setting  to  (Trip), trip after low current detection time setting of . After tripping,
the low current signal remains ON.
6.17.8 Detection of output short-circuit
 : Detection of output short-circuit during start-up
• Function
This parameter detects inverter output short-circuit. It can be usually detected in the length of the
standard pulse. When operating low-impedance motor such as high-speed motor, however, the short-
time pulse should be selected.
=: Detection is executed in the length of the standard pulse every time you start up the inverter.
=: Detection is executed in the length of standard pulse only during the first start-up after putting on
the power or after resetting.
=: Detection is executed with the short-time pulse every time you start up the inverter.
=: Detection is executed with the short-time pulse only for the first time after putting power on or
after resetting.
Function
 or less
F-63
Adjustment range
1-20 (%)
0: Alarm only
1: Tripping
0-100 (%) / (A)
0-255 [s]
ON
OFF

Time [sec]
E6581381
Default setting
10
0
0
0
OFF
6