6.3.7
: Frequency command agreement detection range
: Frequency setting mode selection 1
: Frequency setting mode selection 2
• Function
[Parameter setting]
6
Note: When using VIA terminal, set or respectively to 52 or 53 to put out signals to RY-RC or
Note: This function can be used, for example, to send out a signal indicating whether the amount of
Comparing the frequency command values
If the frequency command value specified using (or ) almost agrees with the
frequency command value from the VIA and VIB terminal with an accuracy of ± , an ON or
OFF signal will be sent out.
Title
Function
Frequency command agreement detection
range
Frequency setting mode selection 1
Frequency setting mode selection 2
FLA-FLB-FLC.
When using VIB terminal, set or respectively to 60 or 61 to put out signals to RY-RC or
FLA-FLB-FLC.
processing and the amount of feedback agree with each other when the PID function is in use.
⇒ For an explanation of the PID function, see section 6.14.
Adjustment range
0.0 ∼ ( Hz)
1-5
F-14
E6581381
Default setting
2.5
1
2