Toshiba TOSVERT VF-FS1 Instruction Manual page 88

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-FS1:
Table of Contents

Advertisement

Setting value
5
Note:
Setting of electronic thermal protection characteristics selection 
Overload protection
×
×
Setting of motor electronic thermal protection level 1  (Same as )
If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor
is smaller than the rated current of the inverter, adjust the electronic thermal protection level 1  so
that it fits the motor's rated current.
* If the indications are in percentages (%), then 100% equals the inverter's rated output current (A).
Output current reduction factor
×1.0
×0.55
[Example of setting: When the VFFS1-2007PM is running with a 0.4kW motor having 2A rated current]
Key operated
LED display


MODE


ENT

⇔
ENT
The rated output current of the inverter should be calculated from the rated current, regardless of the
setting of the PWM carrier frequency parameter ().
Overload stall
×
×
: valid, × : invalid
[%]/[A]
0
30Hz
Note:
The motor overload protection start level is fixed at 30Hz.
Displays the operation frequency. (Perform during operation
stopped.)
(When standard monitor display selection  is set to 
[Operation frequency])
The first basic parameter "" (Wizard function) is displayed.
Press either the
key or the
.
Press the ENT key to display the parameter setting. (Standard
default setting: 100%)
Press the
key to change the parameter to %
(=motor rated current/inverter output rated current x
100=2.0//4.8×100).
Press the ENT key to save the changed parameter.  and the
parameter are displayed alternately.
E-26
E6581381
Output frequency (Hz)
Operation
key to change the parameter to